Application
Heat shrink insulation tape adopts hot melt adhesive and can be used in the insulation protection of high/low switchgear busbar and to repair power cable sheath damage. Its applicable voltage is 36kV.
Item No. | voltage class(kv) | Width(mm) | Thickness(mm) | Packing length(mm) |
CYG-RSD-01 | 1 | 50 | 0.40~0.50 | 5000 |
CYG-RSD-15 | 15 | 50 | 0.80~1.00 | 5000 |
CYG-RSD-36 | 35 | 50 | 1.40~1.80 | 5000 |
CYG-RSD-36(S) | 35 | 50 | 1.40~1.80 | 5000 |
REMARKS: CYG-RSD-36(S) IS SPIRAL SHAPE
SpecificationsProperty | Test Method | Typical Data |
Tensile strength | ASTM D 2671 | >12 MPa |
Ultimate elongation | ASTM D 2671 | ≥400% |
Heat aging Tensile strength Ultimate elongation | 136℃, 168 hrs. | >10 MPa >450% |
Dielectric strength | IEC 243 | ≥20kV/mm |
Dielectric constant | IEC 250 | ≤3.5 |
Volume resistance | IEC 93 | ≥1014Ω .cm |
Copper corrosion | ASTM D 2671/120℃,168hr. | No corrosion |
Cold bend | ASTM D 2671/-40℃,4hrs. | No cracking |
Water absorption | ASTM D570 | < 0.5% |